0,6 / 1 kV 3 × 185 + 1 × 95 LV NETZKABEL
Basisinformation
Modell: YJY
Produktbeschreibung
1. APPLICALBE STANDARDS
Das Kabel muss nach internationalen Normen wie folgt konstruiert, gefertigt und geprüft werden:
Quality Control Standard |
|
ISO 9001 |
Quality Management Systems |
ISO 14001 |
Environmental Management Systems |
Component Material Standard |
|
IEC 60228 |
Conductors of insulated cables |
Cable Standard |
|
IEC 60502-1 |
Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) – Part 1:Cables for rated voltages of 1kV(Um=1.2kV) and 3kV(Um=3.6kV) |
IEC 60332-3-24 |
Test for vertical flame spread of vertically-mounted bunched wires or cables – Category C |
2. KABELSTRUKTUR FÜR 0.6 / 1KV KABEL
1)
CU / PVC / PVC / STA / FR-PVC 0,6 / 1 kV 3 × 185 + 1 × 95
Basic Structure |
Nominal Thickness mm |
Nominal Outer Diameter mm |
1.Copper conductor |
/ |
15.3 |
2.XLPE insulation |
1.6 |
18.5 |
3. Filler |
/ |
42.4 |
4. Wrapping tape |
0.2 |
43.0 |
5. PVC Inner sheath |
1.4 |
45.8 |
6. Galvanized steel tape armor |
0.5 |
47.8 |
7. FR-PVC Outer sheath |
2.6 |
53.0 |
3. TESTANFORDERUNGEN FÜR LV POWER CABLES
Die Kabelprüfung ist gemäß den geltenden Normen der 0,6 / 1kV Netzkabel durchzuführen. Die folgenden Prüfgegenstände sind nach den einschlägigen IEC-Normen durchzuführen.
No. |
Test item |
Routine tests |
|
1 |
measurement of the electrical resistance of conductors |
2 |
Voltage test |
Sample tests |
|
1 |
conductor examination |
2 |
check of dimensions |
3 |
Hot set test for XLPE insulation |
4. VERPACKUNGSPARTIKEL FÜR 0.6 / 1KV POWER CABLES
Die Kabel müssen auf Stahl-Holztrommeln gewickelt werden. Die unauslöschliche Kennzeichnung ist auf der Oberfläche des Trommelflansches entsprechend den Kundenanforderungen zu bedrucken.
Fabrik und AusrüstungPaket
Ort
Unsere Ehre
Produktgruppe : Niederspannungs-Stromkabel